There are several types
of data or information that can be communicated from a HART-enabled
device. This includes:
- Device data
- Supplier data
- Measurement data
- Calibration data
When this data is integrated with control, asset management or
safety systems, you are able to improve plant operations, lower
cost and increase plant availability.
The following is a summary of data items available for communication
between HART Devices and a Host.
Process Variable Values
- Primary Process Variable (analog) - 4-20 ma current signal continuously
transmitted to host
- Primary Process Variable (digital) - Digital value in engineering
units, IEEE floating point, up to 24 bit resolution
- Percent Range - Primary Process Variable expressed as percent
of calibrated range
- Loop Current - Loop current value in milliamps
- Secondary Process Variable 1 - Digital value in engineering
units available from multivariable devices
- Secondary Process Variable 2 - Digital value in engineering
units available from multivariable devices
- Secondary Process Variable 3 - Digital value in engineering
units available from multivariable devices
Commands From Host to Device
- Set Primary Variable Units
- Set Upper Range
- Set Lower Range
- Set Damping Value
- Set Message
- Set Tag
- Set Date
- Set Descriptor
- Perform Loop Test - Force loop current to specific value
- Initiate Self Test - Start device self test
- Get More Status Available Information
Codes vary by manufacturer/device
Status and Diagnostic Alerts
- Device Malfunction - Indicates device self-diagnostic has detected
a problem in device operation
- Configuration Changed - Indicates device configuration has been
changed
- Cold Start - Indicates device has gone through power cycle
- More Status Available- Indicates additional devices status data
available
- Primary Variable Analog Output Fixed - Indicates device in fixed
current mode
- Primary Variable Analog Output Saturated - Indicates 4-20mA
signal is saturated
- Secondary Variable Out of Limits - Indicates secondary variable
value outside the sensor limits
- Primary Variable Out of Limits - Indicates primary variable
value outside the sensor limits
Device Identification
- Instrument Tag - User defined, up to 8 characters
- Descriptor - User defined, up to 16 characters
- Manufacturer Name (Code) - Code established by HCF and set by
manufacturer
- Device Type and Revision - Set by manufacturer
- Device Serial Number - Set by manufacturer
- Sensor Serial Number - Set by manufacturer
Calibration Information for 4-20mA Transmission
of Primary Process Variable
- Date - Date of last calibration, set by user
- Upper Range Value - Primary Variable Value in engineering units
for 20mA point, set by user
- Lower Range Value - Primary Variable Value in engineering units
for 4mA point, set by user
- Upper Sensor Limit - Set by manufacturer
- Lower Sensor Limit - Set by manufacturer
- Sensor Minimum Span - Set by manufacturer
- PV Damping - Primary Process Variable Damping Factor, set by
user
- Message - Scratch pad message area (32 characters), set by user
- Loop Current Transfer Function - Relationship between Primary
Variable digital value and 4-20mA current signal
- Loop Current Alarm Action - Loop current action on device failure
(upscale/downscale)
- Write Protect Status - Device write-protect indicator
|