In general, the installation
practice for HART communicating devices is the same as that for
conventional 4-20mA instrumentation. Individually shielded twisted
pair cable, either in single pair or multi-pair varieties, is the
recommended wiring practice. Unshielded cables may be used for short
distances, if ambient noise and cross-talk will not effect communication.
The minimum conductor size is 0.51mm diameter (#24 AWG) for cable
runs less than 1,524 meters (5,000 ft.) and 0.81mm diameter (#20
AWG) for longer distances.

Typical Wiring Connection using a HART
Field Device, a PC with a PC-based Application
and a Handheld Terminal. Also shown is a required HART Interface
or Modem - either RS232 or USB version.
Grounding
To prevent interference by external signals, it is important to
ground the system properly. In particular, the signal loop should
be grounded, if at all, at one point only. The cable screening must
be connected to ground, at one point only, and must not be connected
to instrument or junction box cases unless these are isolated from
ground. The single ground point will usually be at or near the host
(for example, the control system).
Power supply
Power for a two-wire instrument loop is typically 24V d.c. As always,
the voltage must be sufficient to provide the necessary lift-off
voltage for the field device, taking into account voltage drops
in the cable and load resistor, and a passive IS barrier if one
is present. Smart devices may take up to 22 mA to indicate an alarm
condition; use this value to calculate the worst loop voltage drop.
There are additional communication-related specifications for the
power supply for a HART loop; these are shown in the table below.
The ripple and noise specifications are designed to prevent direct
interference with the HART signals. The impedance limit ensures
that HART signals see the power supply as a low impedance path,
and prevents inadvertent coupling and crosstalk between multiple
HART loops powered from a common supply. (The resistance of output
fuses, if any, must be included, when measuring this value.)
Power supply specification
| Maximum ripple (47 to 125 Hz) |
0.2 V p-p |
| Maximum noise (500 Hz to 10 kHz) |
1.2 mV rms |
| Maximum series impedance (500 Hz to 10 kHz) |
10 Ω |
Cable Length
Most installations are well within the 3,000-meter (10,000 ft) theoretical
limit for HART Communication. However, the electrical characteristics
of the cable (mostly capacitance) and the combination of connected
devices can affect the maximum allowable cable length of a HART
network. The table below shows the affect of cable capacitance and
the number of network devices on cable length. The table is based
on typical installations of HART devices in non-IS environments,
i.e. no miscellaneous series impedance. Detailed information for
determining the maximum cable length for any HART network configuration
can be found in the HART Physical Layer Specifications.
The allowable cable length depends upon the cable capacitance and
the number of network devices.
Cable Length - feet (meters)

To learn more about HART, take our FREE
training course!
|